| Kirish |
| Phase |
Single Phase |
| Power factor |
≥0.99 |
| Kirish chastotasi |
40~70Hz (50/60Hz Auto-Sensing) |
| Nominal Voltage |
208/220/230/240Vac |
| Kirish kuchlanishi diapazoni |
110~300Vac (176~264Vac @ 100% load) |
| Quvvat |
| UPS quvvati |
3000 VA / 2700 W |
| Chiqish |
| Crest factor |
3:1 |
| Power factor |
0.9 |
| O'tish vaqti |
AC mode to Bat.mode: 0ms
Inverter to Bypass: 4ms (Typical) |
| Output Sockets |
Optional: IEC panel/EU panel/UK panel/US panel |
| Chiqish kuchlanishi |
208/220/230/240Vac |
| Output Waveform |
Pure Sinewave |
| Chiqish chastotasi |
Online mode: 46~54Hz or 56~64Hz
Bat. Mode: (50/60±0.1%)Hz |
| Harmonic distortion (THDv) |
≤3% Linear load
≤5% Non linear load |
| Batareya |
| Batareya turi |
Valve Regulated Lead Acid (VRLA) |
| Battery Number |
6 |
| Expandable Runtime |
Yes, External battery pack: DS-UPSB0972B-R/TJC |
| Odatiy zaxira vaqti |
View Runtime Graph |
| Charging Current (Max.) |
1A |
| DC System Voltage (VDC) |
72V |
| Typical Recharging Time |
4 hours (To 90% of full capacity) |
| Capacity (Standard Unit) |
12V/9Ah |
| Fizik parametrlar |
| Net weight (kg) |
26 |
| Dimension W x D x H (mm) |
440 x 600 x 86.5 |
| Indikator |
| Signalizatsiya |
Battery mode/Battery low voltage /Overload/Fault |
| LCD display |
Input voltage, Input frequency, Output voltage, Output frequency, Load percentage, Battery voltage, Inner temperature & Remaining battery backup time |
| Standards |
| Elektromagnit moslik (EMC) |
IEC/EN 62040-2, IEC61000-4-2, IEC61000-4-3, IEC61000-4-4, IEC61000-4-5, IEC61000-4-6, IEC61000-4-8 |
| Xavfsizlik standarti |
IEC/EN 62040-1, IEC/EN 62477-1 |
| Efficiency |
| AC Mode |
92% |
| Battery Mode |
88% |
| Ish muhiti |
| Balandlik (dengiz sathidan) |
<1500m, derating required when>1500m |
| Noise Level |
<55dB at 1 Meter |
| Humidity Range |
20~95%RH @ 0~40℃ (Non condensing) |
| Saqlash harorati |
-25℃~55℃ |
| Ish harorati |
0℃~40℃ |